This 500kW Chiller can be used for the most complete range of cooling applications; from air conditioning to process cooling and even ice rink creation. It can also be used as part of a standalone air conditioning system suitable for temporary events or permanent installation when combined with air handling units.
Interested in hiring this product?
Specification
Performance Data
| Duty : | 500kW |
| Inlet Temperature : | 12°C |
| Outlet Temperature: | 7°C |
| Ambient : | 35°C |
| Compressor Power : | '- |
| EER : | 2.79 |
| Compressors : | 5 |
| Compressor Type: | Scroll |
| Capacity Steps : | '- |
| Control : | Automatic Programme |
| Buffer Tank Capacity : | '- |
| Refrigerant - Type : | R410a |
| Refrigerant - No. Of Circuits : | 2 |
| Evaporator - Type : | Plate |
| Evaporator - No. Of Circuits : | 2 |
| Evaporator - Design Flow: | 78.6m3/hour |
| Evaporator - Pressure Drop: | 52 kPa |
| Evaporator - Max System Pressure: | '- |
| Condenser- Fan Quality: | 8 |
| Condenser - Fan Type: | Axial |
| Water Connection : | 4” Bauer Male & Female |
| Water Pump : | Yes - Lowara FHE40/200/55P |
Electrical
| Power Supply : | 415vAC 3Ø, N + Eth |
| Runing amps : | |
| Power Consumption : | 161 kW/h |
| Full Load Amps : | 386 Amps |
| Start Amps : | 603 Amps |
| Total Current LPA: | |
| Unit Connection : | Hard Wired |
Physical
| Noise Level : | 64 dBA @ 10 Metres |
| Dry Weight : | 3080 kg |
| Dimensions mm (WxLxH) : | 2260 x 4830 x 2430 |