150kW Chiller
The 150kW Chiller is suitable for a complete range of cooling applications – air conditioning process cooling and even ice rink creation.
- Water Outlet Temperature Regulator
- Automatic Fan Circuit Breaker
- Fan Speed Regulator
- Internal Fan Protection Grid
- Water Expansion Vessel
- 3 Bar Water Pump
- Buffer Tank
- Steel Framed
- Electric Board Heater
- Water Strainer
- Electronic Expansion Valve
- Condensing Coil Grid with Metallic Strainer
Interested in hiring this product?
Specification
Performance Data
| Duty: | 152.3kW |
| Inlet Temperature: | 12 °C |
| Outlet Temperature: | 7 °C |
| Ambient: | 35 °C |
| Compressor Power: | 52.5kW |
| EER: | 2.73 |
| Compressors: | 4 |
| Compressor Type: | Scroll |
| Capacity Steps: | 4 |
| Control: | Automatic Programme |
| Buffer Tank Capacity : | 340 Ltrs |
| Refrigerant - Type : | R410a |
| Refrigerant - No. Of Circuits : | 2 |
| Evaporator - Type : | Plate |
| Evaporator - No. Of Circuits : | 2 |
| Evaporator - Design Flow: | '- |
| Evaporator - Pressure Drop: | '- |
| Evaporator - Max System Pressure: | '- |
| Condenser- Fan Quality: | 3 |
| Condenser - Fan Type: | Axial |
| Water Connection: | 2" Bauer Male & Female |
| Water Pump: | Yes - Lowara FHE32/200/55P |
Electrical Data
| Power Supply : | 400-3-50 |
| Running amps : | |
| Power Consumption : | 55.8 kW |
| Full Load Amps: | 131 Amps |
| Start Amps : | 330 Amps |
| Total Current LPA: | |
| Unit Connection : | Hard Wired |
Physical Data
| Noise Level : | 59dB(A) |
| Dry Weight: | 1055 Kg |
| Dimensions mm (WxLxH) : | 1185x3190x1720 |