750kW Chiller

Description

750kW Chiller is our largest chiller, suitable for a wide variety of larger applications & district energy management, fit for emergency recovery or planned maintenance

  • Can be paired with air handling units to provide a complete air conditioning system for temporary events or semi permanent applications
  • Steel framed for resilience & ease of delivery & installation
  • Fully equipped with a water strainer; an electronic expansion valve; a condensing coil grid with metallic filter; a water expansion vessel; and a 3-bar water pump and buffer tank, water outlet temperature regulator, automatic fan circuit breaker & a fan speed regulator, internal fan protection grid & electric board heater.
Performance Data
Duty

750kW

Inlet Temperature

12°C

Outlet Temperature

7°C

Ambient

35°C

Compressor Power

263.5 kW

EER

2.8

Compressors

8

Compressor Type

Scroll

Capacity Steps

8

Noise Level

60 dBA @ 10 Metres

Dry Weight

7500 kg

Dimensions MM (WxLxH)

2384x6527x2555

Control

Automatic Programme

Buffer Tank Capacity

500 Litres

Water Connection

6” Bauer Male & Female

Water Pump

Yes – Lowara FHE32/200/55P

Refrigerant
Type

R410a

No. Of Circuits

4

Evaporator
Type

Plate

No Of Circuits

4

Design Flow

128.3 m3/hour

Pressure Drop

54 kPa

Max System Pressure

4 bar

Condensor
Fan Quantity

6

Fan Type

Axial

Max Air Volume

31.6 m3/second

Electrical
Power Supply

Power Consumption

263.57 kW/h

Full Load Amps

589.6 Amps

Start Amps

929 Amps

Unit Connection

Hard Wired

Optional Ancillary Equipment