150kW Chiller
The 150kW Chiller is suitable for a complete range of cooling applications – air conditioning process cooling and even ice rink creation. In combination with air handling units it can be used to install a stand alone air conditioning system that is suitable for temporary events and permanent installations alike.
- Compressor: scroll type rotary hermetic complete with thermal protection and casing heater.
- 2 3 or 4 capacity steps with high efficiency at partial loads. Water side heat exchanger: with stainless steel plates complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
- Control: microprocessor electronic control with Adaptive Function Plus logic.
Interested in hiring this product?
Specification
Performance Data
| Duty: | 146.3kW |
| Inlet Temperature: | 12 °C |
| Outlet Temperature: | 7 °C |
| Ambient: | 35 °C |
| Compressor Power: | 48.9kW |
| EER: | 2.99 |
| Compressors: | 4 |
| Control: | Automatic Programme |
| Buffer Tank Capacity : | 300 Ltrs |
| Refrigerant - Type : | R410a |
| Refrigerant - No. Of Circuits : | 2 |
| Evaporator - Type : | Plate |
| Evaporator - No. Of Circuits : | 2 |
| Evaporator - Design Flow: | '- |
| Evaporator - Pressure Drop: | '- |
| Evaporator - Max System Pressure: | '- |
| Condenser- Fan Quality: | 3 |
| Condenser - Fan Type: | Axial |
| Water Connection: | 2" Bauer Male & Female |
| Water Pump: | Yes - Lowara FHE32/200/55P |
Electrical
| Power Supply : | 400-3-50 |
| Running amps : | |
| Power Consumption : | 50.4 kW |
| Full Load Amps: | 108.5 Amps |
| Start Amps : | 230.5 Amps |
| Total Current LPA: | |
| Unit Connection : | 5 Pin 125A BS4343 |
Physical
| Noise Level : | 57dB(A |
| Dry Weight: | 1165 kg |
| Dimensions mm (WxLxH) : | 3600x1350x2440 |
Three reasons to choose our service
Equipment tailored to your requirements
Rapid response, 24/7 service and solutions