50kW Low Temperature AHU
50kW low temperature air handling unit for use in conjunction with temporary chillers.
This specialist hire equipment can be used for a range of low temperature applications; from chilled storage and cold stores to spot cooling production areas.
Featuring two powerful fans for efficient and reliable close temperature control. Multiple units can be used to effectively cool even large structures.
- Fully Automatic Controls
- Electric Defrost
- High Airflow Fans
- Operation down to -1.4°C Air Off
Interested in hiring this product?
Specification
Performance Data
| Capacity : | 52.4 kW | 
| Inlet Air Temperature : | 4°C | 
| Outlet Air Temperature : | -4.1°C | 
| Fluid Inlet Temperature : | -8°C | 
| Fluid Outlet Temperature : | -4°C | 
| Max Working Pressure : | 10 Bar | 
| Number of Fans : | 2 | 
| Air Flow: | 13.4 m³/hr | 
| Air Throw: | 2 m | 
| Fluid Velocity : | 0.98 m/s | 
Electrical
| Power Supply : | 415V / 3 / 50 ( V / Ø / Hz) | 
| Plug Type : | 32A 3 Pin BS4343 | 
| Max Fan Absorbed Current : | 2.9 A | 
Physical
| Sound Level : | 83 dBA @ 5 Metres | 
| Weight : | 250 Kg | 
| Dimensions (Length) mm : | 2250 mm | 
| Dimensions (Width) mm: | 915 mm | 
| Dimensions (Height) mm: | 930 mm | 
Three reasons to choose our service
 
				 Equipment tailored to your requirements
 
				 Rapid response, 24/7 service and solutions
 
				  
				

 0808 169 1919
0808 169 1919




 
								 
								 
								 
															 
															