300kW Gas Burner

Description

300kW Gas Burner designed for use in low/medium temperature hot water boilers, hot air or steam boilers, diathermic oil boilers able to respond to any request for residential heating.

  • 300kW Gas fired burner
  • Output: 81-200kW
  • Used in residential heating
  • Low noise level ensured through sound proofing material
  • Microprocessor-based burner safety control box
Servomotor Type
Servomotor Type General

SQN90

Fan Type
Fan Type General

Centrifugal

LPG Gas Delivery
LPG Gas Delivery General

12/24-64 Nm³/h

LPG Gas Density
LPG Gas Density General

0.78 kg/Nm³

Net Calorific Value LPG Gas
Net Calorific Value LPG Gas General

25.8 kWh/Nm³

G25 Gas Density
G25 Gas Density General

0.78 kg/Nm³

G25 Gas Delivery
G25 Gas Delivery General

12/24-64 Nm³/h

Temperature Range
Temperature Range General

0-40⁰C

Net Calorific Value G25 Gas
Net Calorific Value G25 Gas General

8.6 kWh/Nm³

G20 Gas Delivery
G20 Gas Delivery General

10/20-55 Nm³/h

G20 Gas Density
G20 Gas Density General

0.71kg/Nm³

Net Calorific Value G20 Gas
Net Calorific Value G20 Gas General

10kWh/Nm³

Servomotor Run Time
Servomotor Run Time General

12 Seconds

Motor Start up Current
Motor Start up Current General

17 Amps

Heat Output
Heat Output General

101/203-550kW

Power Supply
Power - Supply - General

230v 1ph 50Hz

Burner Operation Mode
Burner Operation Mode General

Two Stage

Control Box
Control Box General

RMG 88.620A2

Noise Level
Sound - Level - General

72 dBA @ 10 mtrs

Total Electrical Power
Total Electrical Power General

0.7kW

Motor Electrical Power
Motor Electrical Power General

0.42 kW

Rated Motor Current
Rated Motor Current General

3.5 Amps

Dimensions (WxDxH)
Dimensions - wxdxh - General

442x859x442mm

Motor Protection Level
Motor Protection Level General

IP 20

Protection Level
Protection Level General

IP 40

CO Emissions
CO Emissions General

<40 mg/kWh

NOx Emissions
NOx Emissions General

<120 mg/kWh

Conforming to
Conforming to General

EN676

Optional Ancillary Equipment