750kW Rhoss Chiller
750kW air cooled chiller ideal for large scale applications. Fitted with an integral pump and tank this unit is suitable for both comfort cooling and process applications.
Utilising a number of these 750kW Chillers in parallel is the perfect option for multi-megawatt requirements.
Interested in hiring this product?
Specification
Performance Data
Duty: | 744 kW |
Inlet Temperature: | 12 °C |
Outlet Temperature: | 7 °C |
Ambient: | 28 °C |
Absorbed Power: | 229.9 kW |
EER: | 2.9 |
Compressors: | 6 |
Compressor Type: | Scroll |
Capacity Steps: | 6 |
Control: | Automatic Programme |
Buffer Tank Capacity : | 980 Ltrs |
Refrigerant - Type : | R410a |
Refrigerant - No. Of Circuits : | 2 |
Evaporator - Type : | Plate |
Evaporator - No. Of Circuits : | 2 |
Evaporator - Design Flow: | |
Evaporator - Pressure Drop: | |
Evaporator - Max System Pressure: | |
Condenser - Fan Quantity : | 10 |
Condenser - Fan Type: | Axial |
Water Connection: | 4" Bauer Male & Female |
Water Pump: | Yes |
Electrical
Power Supply : | 415V 3Ø 50Hz |
Running amps: | |
Power Consumption : | 232.5 kW |
Full Load Amps: | 504.5 A |
Start Amps : | 727.5 A |
Total Current LPA: | |
Unit Connection: | Hard Wired |
Physical
Noise Level : | 64.5 dBA |
Dry Weight: | 3230 Kg |
Dimensions (Length): | 5940 mm |
Dimensions (Width): | 2300 mm |