150kW Chiller

Description

The 150kW Chiller is suitable for a complete range of cooling applications – air conditioning, process cooling and even ice rink creation.

  • Water Outlet Temperature Regulator
  • Automatic Fan Circuit Breaker
  • Fan Speed Regulator
  • Internal Fan Protection Grid
  • Water Expansion Vessel
  • 3 Bar Water Pump
  • Buffer Tank
  • Steel Framed
  • Electric Board Heater
  • Water Strainer
  • Electronic Expansion Valve
  • Condensing Coil Grid with Metallic Strainer
More
Duty

152.3kW

Inlet Temperature

12°C

Outlet Temperature

7°C

Ambient

35°C

Compressor Power

52.5kW

EER

2.73

Compressors

4

Compressor Type

Scroll

Capacity Steps

4

Noise Level

59dBA @ 10 metres

Dry Weight

1055kg

Dimensions MM (WxLxH)

1185x3190x1720

Control

Automatic Programme

Buffer Tank Capacity

240 litres

Water Connection

2” Bauer Male & Female

Water Pump

Yes

Type

R410a

No. Of Circuits

2

Type

Plate

No Of Circuits

2

Design Flow

Pressure Drop

Max System Pressure

Fan Quantity

3

Fan Type

Axial

Power Supply

Power Consumption

55.8kW

Full Load Amps

131 AMPS

Start Amps

330 AMPS

Unit Connection

Hard Wired

Optional Ancillary Equipment